A key aspect to consider for metal materials in explosion-proof electrical equipment is their propensity to ignite explosive gas-air mixtures through mechanical sparks. Research has indicated that the composition of these metals plays a substantial role in their ignition potential. To prevent the occurrence of mechanical spark ignition in metal enclosures, specific elemental limitations are mandated. The standards for explosive environments – General Equipment Requirements – specify the following:
Клас I
In producing RPL level MA or Mb explosion-proof electrical equipment, the composition of aluminum, magnesium, titanium, and zirconium in the enclosure materials must not exceed 15% by mass, and the combined mass percentage of titanium, magnesium, and zirconium must not surpass 7.5%.
Клас II
При производството на взривозащитено електрическо оборудване от клас II общият процент на масата на критичните елементи в материалите на корпуса варира в зависимост от нивото на защита: За оборудване EPLGa общото съдържание на алуминий, магнезий, титан и цирконий не трябва да надвишава 10%, като магнезият, титанът и цирконият не трябва да надвишават общо 7,5%; За оборудване EPLGb общото съдържание на магнезий и титан не трябва да надвишава 7,5%; В случай на оборудване EPLGc, освен вентилатори, капаци на вентилатори и прегради на вентилационни отвори, отговарящи на стандартите EPLGb, няма допълнителни специфични изисквания.
Клас III
При производството на взривозащитени електрически устройства от клас III необходимият общ процент на масата на съответните елементи в материалите на корпуса също варира в зависимост от нивото на защита: За устройствата EPLDa съдържанието на магнезий и титан не трябва да надвишава 7,5%; за устройствата EPLDb се прилага същото ограничение; за устройствата EPLDc, освен вентилатори, капаци на вентилатори и прегради на вентилационни отвори, отговарящи на критериите EPLDb, няма други специални изисквания.