『Click here to download the product PDF: Explosion Proof Anti-Corrosion Plug And Socket BCZ8030』
Technical Parameter
Model and specification | Rated voltage | Rated current | Number of poles | Cable outer diameter | Inlet thread |
---|---|---|---|---|---|
BCZ8030-16 | AC220V | 16A | 1P+N+PE | Φ10~Φ14mm | G3/4 |
AC380V | 3P+PE | ||||
3P+N+PE | |||||
BCZ8030-32 | AC220V | 32A | 3P+PE | Φ12~Φ17mm | G1 |
AC380V | 1P+N+PE | ||||
3P+N+PE | |||||
BCZ8030-63 | AC220V | 63A | 1P+N+PE | Φ18~Φ33mm | G1 1/2 |
AC380V | 3P+PE | ||||
3P+PE 3P+N+PE |
Explosion proof sign | Degree of protection | Degree of protection |
---|---|---|
Ex db e IIB T6 Gb Ex db eb IIC T6 Gb Ex tb IIIC T80℃ Db | IP66 | WF1*WF2 |
Product Features
1. The shell is pressed with glass fiber reinforced unsaturated polyester resin or welded with high-quality stainless steel, which is corrosion resistant, anti-static, impact resistant and has good thermal stability;
2. Exposed stainless steel fasteners with high anti-corrosion performance;
3. The shell is of increased safety type, with explosion-proof switch installed inside;
4. Connect the plug with electrical equipment;
5. The socket is equipped with reliable mechanical interlocking device, that is, the switch can be closed only after the plug is inserted into the socket, and the plug can be pulled out only after the switch is disconnected;
6. The socket is equipped with a protective cover. After the plug is pulled out, the socket is shielded with a protective cover to prevent foreign matters from entering;
7. Steel pipe or cable wiring is acceptable.
Applicable Scope
1. It is applicable to the places in Zone 1 and Zone 2 of explosive gas environment;
2. It is applicable to the places in Zone 21 and 22 of combustible dust environment;
3. Suitable for IIA, IIB and IIC explosive gas environment;
4. Applicable to T1-T6 temperature group;
5. It is applicable to dangerous environments such as oil exploitation, oil refining, chemical industry, gas station, offshore oil platforms, oil tankers, metal processing, etc. as the connection and turning direction change of steel pipe wiring.